FD3G146-2AGP-90
| Nominal Voltage | VAC | 230 |
| Current draw | A | 1.65±10% |
| Speed(RPM) | min-1 | 1750±5% |
| Power consumption | W | 230±10% |
| Max. Air Flow | CFM / m3 /H | 910.41/1547 |
| Max. Static Pressure | In.wg /Pa | 2.08/519 |
50pcs
When a 146 mm dual inlet blower has to move more than 1500 m3/h while still running from a single-phase wall supply, the FD3G146-2AGP-90 is the unit that removes the need for a fan array. Its 230VAC EC92 BLDC motor with integrated drive delivers 910.41 CFM (1547 m3/h) at 1750 RPM and 230 W, producing 2.08 in.wg (519 Pa) of static pressure, so one blower can replace two or three smaller AC belt-driven assemblies in an air handling cabinet. The two superpowers here are raw delivered airflow per footprint and mains-direct EC operation: 184~270VAC input range means the same blower works on 208V, 220V, 230V and 240V systems without a step-down transformer, and the integrated drive removes the external VFD, contactor and thermal overload stack that an AC equivalent needs. Speed and airflow are trimmed through a 0~10VDC or PWM control input, with FG tach output available for closed-loop monitoring, and the standard control protocol can be swapped for Modbus485 communications when the blower is part of a building management network. The impeller is galvanized steel sheet on a 146 mm diameter, paired with a die-cast aluminum end cap and housing that holds bearing alignment under continuous load and resists the corrosion seen in humid plant rooms. Electrical protection and insulation follow the EC92 drive platform, with 1.65 A current draw at nominal conditions and a 20AWG, 209 mm cable flying lead for direct connection to a terminal box or controller. Typical installations are packaged air handling units, heat recovery ventilation, cleanroom and laboratory supply/extract boxes, drying and process air cabinets, and telecom or equipment room cooling where constant pressure control is required. The blower is CE and RoHS compliant and is built in an OEM/ODM factory that supports custom cable lengths, connector types and Modbus485 firmware configuration for volume programs.
The FD3G146-2AGP-90 is a dual inlet centrifugal blower built around a 146 mm impeller formed from galvanized steel sheet. The double inlet, double width impeller uses a forward-curved blade set with a high blade count to generate pressure at moderate tip speed, and the galvanized coating provides a zinc barrier that resists rust in condensing airstreams without the cost penalty of stainless steel. Each impeller is dynamically balanced after assembly so that residual vibration stays low at the 1750 RPM design point, protecting the motor bearings and limiting structure-borne noise in the host cabinet. The rotor diameter of 92 mm matches the EC92 motor platform, giving a compact hub with a short shaft overhang and reduced bending moment at the impeller. The end cap and housing are die-cast aluminum, chosen for stiffness and heat rejection: the casting carries the bearing seats and motor mount in one dimensionally stable part, so shaft alignment is held over the service life, and the aluminum surface conducts drive heat away from the winding. The motor is a three-phase BLDC design with an integrated EC92 drive mounted to the casting; hall sensors commutate the stator and the drive performs sinusoidal current shaping to keep torque ripple and audible whine low. Electrical ratings are 230VAC nominal with an operating window of 184 to 270VAC at 50/60 Hz, drawing 1.65 A and consuming 230 W at the rated operating point. Speed control accepts a 0 to 10VDC analog signal or a PWM duty input, and the factory default configuration can be exchanged for Modbus485 communications so the blower can report status and accept speed setpoints over an RS485 bus; FG tach output is provided as standard for rpm feedback. The electrical interface is a 20AWG flying lead, 209 mm long, with the conductor gauge sized for the 1.65 A running current and for the inrush seen during start; lead length and termination can be customized for OEM builds. The bearings are preloaded ball bearings selected for the axial and radial loads of a double inlet impeller, with a calculated L10 life suitable for continuous HVAC duty and grease retained for life, so no relubrication access is needed. Protection features inside the drive include over-current, over-voltage, under-voltage, locked rotor and over-temperature limiting, with automatic restart after a fault clears. Acoustic output is 74 dB(A) at the rated point, measured at the standard test position; the dual inlet geometry spreads the sound across two volute cut-offs, which reduces the discrete tone compared with a single inlet blower of the same output. Maximum airflow is 910.41 CFM (1547 m3/h) and maximum static pressure is 2.08 in.wg (519 Pa), so the blower holds flow through long duct runs, high-efficiency filters and multi-outlet plenums. The assembly is CE and RoHS compliant, and production units are run-tested for speed, current and vibration before packing; the manufacturing line is an OEM/ODM operation able to support custom labeling, alternative control firmware and volume-specific acceptance testing.
| EC Dual Inlet Centrifugal Blower | ![]() |
|
| Type | FD3G146-2AGP-90 | |
| Model | BLDCEC92 | |
| Nominal Voltage | VAC | 230 |
| Voltage range | VAC | 184~270 |
| Current draw | A | 1.65±10% |
| Speed(RPM) | min-1 | 1750±5% |
| Power consumption | W | 230±10% |
| Sound Pressure Level | dB(A) | 74±5% |
| Max. Air Flow | CFM / m3 /H | 910.41/1547 |
| Max. Static Pressure | In.wg /Pa | 2.08/519 |
| Insulation class | ~ | Class B |
| Degree of protection | ~ | IP44 |
| Control Input | ~ | 0~10VDC / PWM |
| Signal Output | ~ | FG (Tach output ) |

Remarks:
Ⅰ. Standard cable length Refer to the figure below. The length of cable can be customized
Ⅱ. Conventional mode is 0-10V/PWM control, can optionally replace the communication protocol, detailed communication protocol, please contact technical personnel


Test condition:
Ⅰ.The test data is obtained under the specified environment conditions and installation mode
Ⅱ.Input Voltage---Operating voltage
Ⅲ.Temperature---Room temperature 25℃
Ⅴ.Humidity---65%RH
Ⅰ.When taking out the fan, do not directly lift the fan lead wire. If the lead wire is excessively stressed, the internal welding part may fall off
Ⅱ.Do not plug or unplug the fan lead plug when the fan is running
Ⅲ.If the fan does not work after starting, do not touch the impeller, rotor, or other parts, professional technical personnel are required to inspect the fan to prevent sudden start of the fan from causing hand or other personal injury
Ⅳ.The power line and control line of the fan cannot be connected in reverse, otherwise it will burn out
Ⅴ.Because of the soft start characteristics of the fan, to prevent personal injury, do not touch the impeller or other parts of the fan during powered on or running at low speeds
Ⅵ.The fan needs to be operated and used under the guidance of professional personnel to prevent children from coming into touch this product
Ⅶ.If the power line is worn or damaged, it needs to be returned to the manufacturer for repair or be replaced under the guidance of the manufacturer
Ⅷ.As a part of the fan, it is not recommended to use the motor alone when there is no impeller or loading
1. High Efficiency: The FD3G146-2AGP-90 delivers 1547 m3/h at 519 Pa while drawing only 230W, achieving 30-40% energy savings over equivalent AC fans through FANOVA's BLDC motor technology.
2. Industrial-Grade Impeller: The 146mm galvanized steel sheet impeller resists corrosion, wear and high temperatures, making the fan suitable for harsh industrial environments and corrosive gas streams.
3. Wide Application Range: Suitable for industrial ventilation, dust extraction, HVAC units, agricultural ventilation and new-energy equipment, offering flexible customized solutions (OEM/ODM).
4. Sustainable Development: Low-voltage DC operation enables direct solar and battery integration; recyclable steel impeller and optimized BLDC drive meet eco-friendly requirements with long-term reliability.
5. Easy Installation and Maintenance: Compact 146mm footprint, 0-10VDC/PWM speed control, FG tach output and standard cable make the fan simple to wire, control and service.
Q1:What kind of payments do you support?
A1: For sample order, 100% payment in advance; For batch order, 30% in advance and 70% will be paid before shipping
Q2.Will you provide samples?
A2: Sample is available and can be delivered within 10days
Q3:How can I choose a more suitable model?
A3: We need the information like fan type, quantity, size, material, voltage, air flow and static pressure.
Q4:How can I place the order?
A4: Usually quote you within 24 hours after we get your inquiry. First sign the PI,pay deposit,then we will arrange the production.After finished production need you pay balance. Finally we will ship the Goods.
Q5:About transportation
A5: All available shipping ways could be applied, express shipping, air or sea. Appointed shipping company or our own forwarders all could be used in shipment. Full-way tracking the cargos for you before the goods arrive.
Q6:How long is the warranty period?
A6: We currently offer 3-year quality guarantee for our own products, and in response to current product problems, our company provides line support, and some customers have been able to improve their products.